Four Conductor Power Cables 0,6/1kV Armoured & Sheated

Three Conductor Power Cables 0,6/1kV Armoured & Sheated
May 18, 2020
Five Conductor Power Cables 0,6/1kV Armoured & Sheated
May 18, 2020

Four Conductor Power Cables 0,6/1kV Armoured & Sheated

Certificates:

Application

These cables are intended for use as control and power cables aboard ship and on off-shore oil rings. The cables are constructed in accordance with the recommended practice for marine cable for use on fixed or floating facilities, IEEE 1580. Excellent resistance to oil, abrasion petrochem fluids, moisture salty water and sunlight.

Download Pdf

CONDUCTOR : Soft annealed stranded bare or tinned copper per IEEE1580
SEPARATION TAPE : Polyester tape if required
INSULATION / JACKET : Type P flame retardant cross-linked polyolefin compound, X110 meeting the requirements for IEEE 1580 Type P and UL1309
JACKET : CPE, Flame retardant, oil abrasion, chemical resistant thermosetting compound as required IEEE1580
ARMOR : Basket weave bronze wire armour per IEEE1580 and UL1309/ CSA C22.2 No.245. Tinned copper wire available by request
SHEATH : CPE, Flame retardant, oil abrasion, chemical and sunlight resistant thermosetting compound as required IEEE1580
OUTER SHEATH COLOR : Black
REFERENCE STANDARD : IEEE 1580, UL 1309, CSA C22.2 No.245
TEMPERATURE RATİNG : Untel 125°C / UL CSA 110°C / IEEE 100°C
FLAME RETARDANT : IEEE 1202 & IEC 60332-3 cat. A
COLD BEND/IMPACT : -40°C / -35°C (CSA 22.2 No.03)
Size AWG Diameter (inches) Weight (lbs/Mft) 110ºC A 100ºC A
160.5832211413
140.6192622220
120.6683232625
100.7343903433
80.9215914442
61.0178085956
41.25812367774
21.417167710198
11.5552144119114
1/01.752434137131
2/01.8593050158150
3/02.044003183175
4/02.2494670211202
2622.495610249235
3132.6596395302289
3732.8387576302289
4443.0028760348329
5353.33810570371354
6463.6211840432413
 
Seabright SA